diff --git a/docs/source/control/drive/reference_gen.md b/docs/source/control/drive/reference_gen.md index f4735065..f223d285 100644 --- a/docs/source/control/drive/reference_gen.md +++ b/docs/source/control/drive/reference_gen.md @@ -20,7 +20,7 @@ where $\hatabspsiR$ is the rotor flux magnitude estimate and $\ismax$ is the max --- label: im_bd_lim --- - \tau_\mathrm{M}^\mathrm{b} = \frac{3\np}{2} \frac{(\abspsisref)^2}{2\hat{L}_\ell} + \tau_\mathrm{M}^\mathrm{b} = \frac{3\np}{2} \frac{(\abspsisref)^2}{2\hat{L}_\ell} ``` where the leakage inductance estimate can be expressed by means of the inverse-Γ parameters as $\hat L_\ell = [(\hatLM + \hatLsgm)/\hatLM]\hatLsgm$. @@ -35,7 +35,7 @@ width: 100% align: center alt: Reference generation for induction machines --- -*Figure 1:* Reference generation for induction machines, including field weakening, current limitation (CL), and breakdown torque limitation. The limited torque reference is denoted by $\overline{\tau}_\mathrm{M}^\mathrm{ref}$ and the rated stator flux by $\psi_\mathrm{s}^\mathrm{nom}$. The parameter $k_\mathrm{u}$ is the voltage utilization factor. +*Figure 1:* Reference generation for induction machines, including field weakening, current limitation (CL), and breakdown torque limitation. The limited torque reference is denoted by $\overline{\tau}_\mathrm{M}^\mathrm{ref}$ and the rated stator flux by $\psi_\mathrm{s}^\mathrm{nom}$. The parameter $k_\mathrm{u}$ is the voltage utilization factor. ``` ```{figure} ../figs/im_ref_gen.svg @@ -45,7 +45,7 @@ width: 100% align: center alt: Reference generation for induction machines --- -*Figure 1:* Reference generation for induction machines, including field weakening, current limitation (CL), and breakdown torque limitation. The limited torque reference is denoted by $\overline{\tau}_\mathrm{M}^\mathrm{ref}$ and the rated stator flux by $\psi_\mathrm{s}^\mathrm{nom}$. The parameter $k_\mathrm{u}$ is the voltage utilization factor. +*Figure 1:* Reference generation for induction machines, including field weakening, current limitation (CL), and breakdown torque limitation. The limited torque reference is denoted by $\overline{\tau}_\mathrm{M}^\mathrm{ref}$ and the rated stator flux by $\psi_\mathrm{s}^\mathrm{nom}$. The parameter $k_\mathrm{u}$ is the voltage utilization factor. ``` ## For Synchronous Machines @@ -62,7 +62,7 @@ width: 100% align: center alt: Reference generation for synchronous machines --- -*Figure 2:* Optimal reference generation for synchronous machines, including field weakening, maximum-torque-per-ampere (MTPA), maximum-power-per-voltage (MTPV), and current limitation (CL). These are single-dimensional lookup tables, see the example in [Figure 2](fig:flux_vs_torque). Two-dimensional transformation to the current reference is needed only in the case of current-vector control. +*Figure 2:* Optimal reference generation for synchronous machines, including field weakening, maximum-torque-per-ampere (MTPA), maximum-power-per-voltage (MTPV), and current limitation (CL). These are single-dimensional lookup tables, see the example in [Figure 2](fig:flux_vs_torque). Two-dimensional transformation to the current reference is needed only in the case of current-vector control. ``` ```{figure} ../figs/sm_ref_gen.svg @@ -72,7 +72,7 @@ width: 100% align: center alt: Reference generation for synchronous machines --- -*Figure 2:* Optimal reference generation for synchronous machines, including field weakening, maximum-torque-per-ampere (MTPA), maximum-power-per-voltage (MTPV), and current limitation (CL). These are single-dimensional lookup tables, see the example in [Figure 3](fig:flux_vs_torque). Two-dimensional transformation to the current reference is needed only in the case of current-vector control. +*Figure 2:* Optimal reference generation for synchronous machines, including field weakening, maximum-torque-per-ampere (MTPA), maximum-power-per-voltage (MTPV), and current limitation (CL). These are single-dimensional lookup tables, see the example in [Figure 3](fig:flux_vs_torque). Two-dimensional transformation to the current reference is needed only in the case of current-vector control. ``` ```{figure} ../figs/flux_vs_torque.svg @@ -83,7 +83,7 @@ width: 100% align: center alt: Example of optimal reference characteristics --- -*Figure 3:* Example of optimal reference characteristics for a 5.6-kW PM-SyRM. +*Figure 3:* Example of optimal reference characteristics for a 5.6-kW PM-SyRM. ``` ```{figure} ../figs/flux_vs_torque.svg @@ -93,5 +93,5 @@ width: 100% align: center alt: Example of optimal reference characteristics --- -*Figure 3:* Example of optimal reference characteristics for a 5.6-kW PM-SyRM. +*Figure 3:* Example of optimal reference characteristics for a 5.6-kW PM-SyRM. ```