Description
Issue overview
This field is set to zero in the library file:
OS:WaterHeater:Sizing,
{b8e4780a-96a8-4f09-8b96-e7ab94bbd0f1}, !- Handle
{db2fa640-2a72-4846-9027-769207ea3ebf}, !- WaterHeater Name
PeakDraw, !- Design Mode
0.538503, !- Time Storage Can Meet Peak Draw {hr}
0, !- Time for Tank Recovery {hr}
1; !- Nominal Tank Volume for Autosizing Plant Connections {m3}
, which causes a fatal error:
** Fatal ** SizeTankForSupplySide: Tank="WATER HEATER STRATIFIED 200GAL 9KW", requested sizing for max capacity but entered Recovery Time is zero.
Current Behavior
Expected Behavior
Steps to Reproduce
Possible Solution
Recommend this value be set to the industry standard of 1 hour.